Low consumption EASYPACK-I

TCAIY-THAIY 270÷2130

Cooling capacity: 67.1÷130.4 kW

Heating capacity: 71.2÷134.6 kW

WEBCODE: EAI01

Product benefits

  • Chillers and heat pumps with inverter compressors featuring a class A rating
  • Precise and efficient power modulation
  • Plug&Play unit with integrated hydronic module and heat recovery
  • Integrated MASTER/SLAVE control
Inverter_logo GreenLine_logo Garanzia3_logoFR
  • SoloRaffr_logo
  • PdC_logo
  • Install_EST_logo
  • R410A_logo
  • IntCert2
  • CE_logo
  • Eurovent_logo
  • Bureau_Veritas_logo

Packaged air-cooled water chillers and reversible heat pumps with axial fans. Range with hermetic scroll compressors, DC Inverter and R410A refrigerant.



Construction features

• Compressor: scroll type, rotary, hermetic and with Inverter actuation (1+i) complete with thermal protection and casing heater.
• Continuous regulation with high efficiency at partial loads.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring micro-channels or finned coil with copper pipes and aluminium fins depending on models/sizes.
• Fan: external rotor axial type electric fans with internal thermal protection of accident protection grilles. The electric fans, based on the sizes, are EC fans or fitted with a proportional electronic device for continuous regulation of the rotation speed.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.


Versions

• T - High efficiency version with oversized condensing section (TCAITY-THAITY).
• Q - Super-silenced version complete with compressor technical compartment soundproofing, reduced speed fans and oversized condensing section (TCAIQY-THAIQY).


Models

• TCAITY: high efficiency unit designed for cooling only.
• TCAIQY: super silenced unit designed for cooling only.
• THAITY: heat pump unit.
• THAIQY: super silenced heat pump unit.


Factory fitted accessories

• PUMP with single or double electric pump, including an automatic pump in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with integrated 230 - 440 litre buffer tank (depending on the sizes) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• VPF control.
• Desuperheater.
• 100% heat recovery unit.
• Condensing control with fans with EC motor (standard in sizes 270÷2100).
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Technical compressor compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Microchannel coils with E-coating treatment, copper/copper or pre-painted copper/aluminium depending on the versions.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Interfaces for serial communication with other devices.
• Rubber anti-vibration mounts.


Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.


TCAITY-TCAIQY MODEL
Nominal cooling capacity kW
Nominal cooling capacity kW
E.E.R.
E.E.R.
Absorbed power kW
Absorbed power kW
THAITY-THAIQY MODEL
Nominal heating capacity kW
Nominal heating capacity kW
C.O.P.
C.O.P.
Nominal cooling capacity kW
Nominal cooling capacity kW
Absorbed power kW
Absorbed power kW
TCAIY-THAIY MODEL
TCAITY-THAITY sound pressure dB(A)
TCAIQY-THAIQY sound pressure dB(A)
TCAITY-THAITY sound power dB(A)
TCAIQY-THAIQY sound power dB(A)
Scroll/step compressor no.
Circuits no.
Electrical supply V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width mm
H - Height mm
P - Depth mm
TCAITY weight kg
THAITY weight kg
SEASONAL ENERGY PERFORMANCE
TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW
SEER  (EN 14825)
ηs,c %
TCAIQY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW
SEER  (EN 14825)
ηs,c %
THAITY MODEL SEASONAL ENERGY PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW
SCOP (EN 14825)
ηs %
Energy class
THAIQY MODEL SEASONAL ENERGY PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW
SCOP (EN 14825)
ηs %
Energy class
270 280 290 2100 2115 2130
69,8 82,6 90,3 97,9 117 130,4
67,8 80,8 87,7 93,4 111,4 125,5
3,16 3,17 3,15 3,02 3,10 3,14
3,01 3,06 3,00 2,84 2,90 3,01
22,09 26,06 28,67 32,42 37,74 41,53
22,52 26,41 29,23 32,89 38,41 41,69
270 280 290 2100 2115 2130
73,4 85,4 92,5 100,6 121,5 134,6
71,2 83,4 90,4 98,7 117,4 130,6
3,37 3,34 3,36 3,34 3,37 3,32
3,31 3,33 3,32 3,30 3,34 3,36
67,1 79,3 86,8 93,5 112,6 126,5
65 77,9 84,7 90,3 108,6 123,5
21,78 25,57 27,53 30,12 36,05 40,54
21,51 25,05 27,23 29,91 35,15 38,87
270 280 290 2100 2115 2130
52 53 53 53 55 56
45 46 46 46 49 50
84 85 85 85 87 88
77 77,5 77,5 77,5 81 82
1+i / continuous regulation 1+i / continuous regulation 1+i / continuous regulation 1+i / continuous regulation 1+i / continuous regulation 1+I / continuous regulation
1 1 1 1 2 2
400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
270 280 290 2100 2115 2130
3250 3250 3250 3250 3450 3450
1540 1540 1540 1540 2000 2000
1210 1210 1210 1210 1520 1520
765 790 795 800 1125 1145
880 915 920 925 1325 1345
270 280 290 2100 2115 2130
69,8 82,6 90,3 97,9 117 130,4
4,45 4,55 4,53 4,49 4,19 4,17
175 179 178 176 165 164
67,8 80,8 87,7 93,4 111,4 125,5
4,36 4,45 4,39 4,33 4 4,04
172 175 173 170 157 159
71 78 85 92 121 126
4,09 4,18 4,16 4,16 3,99 4,03
161 164 164 163 156 158
- - - - - -
64 77 83 91 111 133
3,99 4,08 4,04 4,06 3,88 3,96
156 160 159 159 152 155
A++ - - - - -

Data at the following conditions:

Air: 35°C - Water: 12/7°C

Air: 7°C, D.B. - 6°C W.B.- Water: 40/45°C.

In open field (Q = 2) at 10 m from the unit on the coil side.

Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.

Weight referred to the unit without load and not accessorised.

TCAIQY-THAIQY super-silenced versions.

Performance according to EN 14511:2013.

Low temperature application (7°C)

Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

In Average climatic conditions, low temperature application (35°C)

Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/213 and No.813/2013)